Sanitary Pressure Transmitters

Standard Specifications

For The LSPT-4220 Sanitary Pressure Transmitters / Pressure Sensors


• Accuracy : 0.50% BFSL

• Repeatability : 0.07%

• Hysteresis : 0.15% or better

• Linearity : ±0.08 BFSL or better

• Stability : ±0.2% of calibrated rage for 1 year

• Over-Range Rating : 2 times base range at burst of 800%

• Zero/Span Adjustments : ±10%

• Process Temperature Range : -20˚F to 300˚F

• Storage Temperature : -65˚F to 250˚F

• Operating Temperature : -0˚F to 180˚F

• Durability : 10 to the 7th cycles with negligible performance change

• Humidity Effect : no performance effect at 95% relative humidity non-condensing

• Vibration Sweep : less than ±0.1% F.S. effect for 0-2000HZ at 20 g’s in any axis

• Shock : less than ±0.05% F.S. effect for 100g’s 20ms shock in any axis

• Position Effect : less than 0.1%F.S.

• Output : 4 to 20mA standard output; optional 1-5VDC, 1-6VDC reverse polarity protected

• Housing : highly polished 304 s.s.; product contact surfaces 316 s.s.

• Approvals : meets ALL 3A, USDA and FDA requirements