WFLTV-DM2011 — DIN Rail Mounting Level Control

LUMENITE MODEL WFLTV-DM2011DIN RAIL MOUNTING LEVEL CONTROLL1HLGL2NCNOCVAR. SENS.NOT USEDLH110V AC LINELOADCONNECT TO LOAD POWER SOURCECONNECT THE "G" GROUND TERMINAL TO THETANK, GOOD EARTH GROUND OR A GROUNDPROBE.SEQUENCE OF OPERATION.1. WHEN LIQUID FALLS BELOW THE LOW LEVEL PROBE, THE LOAD COMES ON. WHEN LIQUID REACHES THE HIGH LEVEL PROBE, THE LOAD GOES OFF.2. FOR REVERSE OPERATION, REMOVE WIRE FROM THE NORMALLY CLOSED (NC) TERMINAL AND CONNECT TO THE NORMALLY OPEN (NO) TERMINAL.3. IF THE LOW LEVEL PROBE IS NOT CONNECTED, THE 201 SERIES PROVIDES SINGLE LEVEL ON/OFF OPERATION.LUMENITE CONTROL TECHNOLOGY2331 N 17th Ave. Franklin Park, IL 60131PH : 1-847-455-1450 Intl. PH : 0011-847-455-1450FX : 1-847-455-0127E-Mail : customerservice@lumenite.comWeb : lumenite.com

FLTV-201 Combination — Liquid Level Control

LUMENITE ELECTRONIC LIQUID LEVEL CONTROL.SERIESFLTVMODEL201TYPEVariableCIRCUITS1PDTVOLTAGE50/60 CY.SENSITIVITY100KSWITCH AMPERES10Amps @ 110VACLIQUIDConductiveSENSITIVITY KNOBLINE V. 50/60 CY.LOADLINE OR SEPARATEVOLTAGE, SEE NOTE12345678WT.BK.PROBE ASSEMBLYHI.LOWPROBE LEAD-IN CABLE MUST NOT BE INCLOSEDWITH POWER OR LOAD WIRES.CONNECT POST #8 TO ANYGOOD GROUND OR GRD.PROBE IF SUPPLIED.NOTE: GROUND POST #8 IS A REFERENCEFOR THE SENSING CIRCUIT. DO NOTCONNECT TO COMMON OF LINE POWEROR GROUND OF ANY POWER SOURCE.SEQUENCE OF OPERATION.1. WITH THE HIGH LEVEL PROBE TOUCHING THE LIQUID, TURN SENSITIVITY KNOB RIGHT OR LEFT UNTIL LOAD COMES "ON".2. NORMAL OPERATION: LOAD "ON" WHEN LIQUID TOUCHES THE HIGH LEVEL PROBE. LOAD "OFF" WHEN LIQUID FALLS BELOW THE LOW LEVEL PROBE.3. FOR REVERSE OPERATION - REMOVE WIRE FROM POST #4 AND CONNECT IT TO POST #3.4. NOTE: IF LOAD EXCEEDS 1/4 H.P. SINGLE PHASE, OR FOR ANY THREE PHASE LOAD - USE MAGNETIC MOTOR STARTER.*** WHEN SENSITIVITY KNOB IS AT ZERO - UNIT WILL NOT OPERATE IN WATER.LUMENITE CONTROL TECHNOLOGY2331 N 17th Ave. Franklin Park, IL 60131PH : 1-847-455-1450 Intl. PH : 0011-847-455-1450FX : 1-847-455-0127E-Mail : customerservice@lumenite.comWeb : lumenite.com

FLT-3074-F-2C-2MS-PWP — Sequence of Operation

MODEL: FLT-3074-F-2C-2MS-PWPSEQUENCE OF OPERATION: SELECTOR SWITCHES IN AUTO POSITION.Line Voltage: 440VACSENSITIVITY: 400KCYCLE #1WHEN LIQUID REACHES MIDDLE LEVEL PROBE, PUMP #1 GOES ON.WHEN LIQUID FALLS BELOW LOW LEVEL PROBE PUMP #1 GOES OFF.CYCLE #2THIS CYCLE IS THE SAME AS #1 EXCEPT PUMP #2 OPERATES.IF LIQUID REACHES HIGH LEVEL PROBE, BOTH PUMPS OPERATE UNTILLIQUID FALLS BELOW LOW LEVEL PROBE.ALARM AND LIGHT COME ON AT HIGH LEVEL.PUMP #1 SELECTOR SWITCHAUTOOFFMANBELLPUMP #2 SELECTOR SWITCHAUTOOFFMANSIGNAL LIGHTBELL STOP BTNTERMINALS:Note : Terminals 1-6 are pre-wiredby Lumenite®. For contactorinstructions, see attached schematics.12345678910HIGHMIDLOWPROBESCONNECT POST #7 TO GOOD EARTHGROUND OR GROUND PROBE IF PROVIDED.Lumenite® Control Technology, Inc.2331 N 17th Ave. Franklin Park, IL 60131PH : 1-847-455-1450 Intl. PH : 0011-847-455-1450FX : 1-847-455-0127E-Mail : customerservice@lumenite.com Web : lumenite.com

FLT-307-2C-2MS-F (OPTIONAL) — Wiring Schematic

FLT-307-2C-2MS-FLOW MID LEVELTOP HIGH LEVELBUTTON STRAIGHT12VDC12VDCLRLATCHING RELAYN.O. PUSH BUTTONLIGHTBELBELLAUTOOFFMANAUTOOFFMANAUTOOFFMAN1LINE2LATCHING RELAY3A24AUTO-OFF-MAN5YELLOW #26YELLOW7GND8ORANGE9MID PROBE10HIGH PROBELINEA2PROPRIETARY — INTERNAL USE ONLY

AF(C)26...38 Contactor — Instructions

Acc. to UL60947-4-1 and CSA C22.2NO. 60947-4-1, for use on a circuitcapable of delivering not more than themax. symmetrical amperes at the max.voltage shown in the table below.WARNING: If opening of BCP, controllershall be examined and replaced if damaged.MAX SHORT-CIRCUIT AT 480 V, 600 V (kA)AF(C)26fuse 60 A/RK5AF(C)30...38fuse 100 A/RK5AF(C)26...38100 A/JAF(C)26...38 Circuit BreakerXTZV125 (125 A): 480 V = 100 kA / 600 V = 42 kAMOUNTING ON DIN RAIL135 mm rail23CLICK!4CONTROL CIRCUIT TERMINALS A1-A2Uc >= 24 V, 50/60 HzAF26...38(Z)(B)Uc >= 20 V DCAF26...38(Z)(B)Uc = 48-130 V, 50/60 Hz-DCAF26...38...-12Uc = 24-60 V, 50/60 HzAF26...38Uc = 12-20 V DCAF26...38ZUc = 24...230-240 V 50 HzAFC26...38Uc = 24...240-260 V 60 HzATTENZIONE: TENSIONE PERICOLOSA. FARE RIFERIMENTO ALLE ISTRUZIONI PER L'USO. PRIMA DI INTERVENIRE SU QUESTO DISPOSITIVO,SCOLLEGARE E ISOLARE TUTTE LE FONTI DI ALIMENTAZIONE. L'INSTALLAZIONE DEVE ESSERE ESEGUITA DA UN INSTALLATORE QUALIFICATO.Acc. to UL60947-4-1 and CSA C22.2NO. 60947-4-1 min. enclosure forAF(C)26...38(Z)(B): 255 x 180 x 175 mmAF(C)26...3835 mm DIN rail — EN/IEC 60715AF(C)26...38(Z)(B)-30-00Pos. 1, 2, 3, 4 + max 6 aux. contacts / 4NC**Pos. 1 +/- 30° · Pos. 5 + max 6 aux. contacts / 3NC**!CC4: max 1x CC4-10 + max 1x CC4-01CC4-01: ** max NC-1AUX. CONTACT POSITIONSPos. 1Pos. 2Pos. 3Pos. 4Pos. 5+/-30°+/-30°Pos. 1: front mount, tilted max +/- 30°Pos. 5: side mount, max 6 aux. contacts / 3NC**AF(C)26...38(B)-30-00AF(C)26...38(B)→ TF42 / EF19 / EF45↓ CAL4-11CAT4-11 →CA4 / CC4ASSEMBLY STEPS12345CLICK!CONTROL SUPPLYUc = 12-20 V DCA1 (+)A2 (-)Electronic coil control: Uc must be withinrated range for reliable operation.TERMINAL CONNECTIONSSCREWTORQUEWIRE HOLEM3.51.2 Nm (11 Lb.in)ø 5.5 mm (0.22 in)M42.5 Nm (22 Lb.in)ø 6.5 mm (0.26 in)Tool: Pozidriv N°WIRE GAUGEAWG 14-10: 1 or 2 x 2.5...4 mm² (Solid/Stranded)AWG 14-8: 1 or 2 x 2.5...10 mm² (Solid/Stranded)1 or 2 x 0.75...2.5 mm²1 x 0.75...2.5 mm²2 x 0.75...1.5 mm²STRIP LENGTHS10 mm (0.39 in)14 mm (0.55 in)< 8 mm (0.31 in) ferruleCAL4-11 / CAT4-11 auxiliary contact blocks:connect per applicable local electrical code.